B.3 Parameter Table
No.(Addr.)
Name
E1-04
Maximum Output Frequency
(303H)
E1-05
Maximum Voltage
(304H)
E1-06
Base Frequency
(305H)
E1-07
Middle Output Frequency
(306H)
E1-08
Middle Output Frequency Voltage
(307H)
E1-09
Minimum Output Frequency
(308H)
E1-10
Minimum Output Frequency
(309H)
Voltage
E1-11
(30AH)
Middle Output Frequency 2
<11>
E1-12
(30BH)
Middle Output Frequency Voltage 2
<11>
E1-13
Base Voltage
(30CH)
<2> Default setting is dependent on the control mode (A1-02) and the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
<9> Values shown here are for 200 V class drives. The default is 400 V when using a 400 V class drive.
<11> Parameter is ignored when E1-11 and E1-12 are set to 0.0.
<13> Auto-Tuning will set E1-13 to the same value as E1-05.
<33> Setting range depends on the type of motor being used. CLV allows a setting range of 10.0 to 120.0 Hz, while CLV/PM allows a setting range
of 4.0 to 120.0 Hz.
E2: Motor Parameters
No.(Addr.)
Name
E2-01
Motor Rated Current
(30EH)
E2-02
Motor Rated Slip
(30FH)
E2-03
Motor No-Load Current
(310H)
E2-04
Number of Motor Poles
(311H)
E2-05
Motor Line-to-Line Resistance
(312H)
E2-06
Motor Leakage Inductance
(313H)
E2-07
Motor Iron-Core Saturation
(314H)
Coefficient 1
E2-08
Motor Iron-Core Saturation
(315H)
Coefficient 2
E2-09
Motor Mechanical Loss
(316H)
346
All Modes
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the
setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these
rules:
E1-09 ≤ E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above conditions do not
apply.
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
Note: Some parameters may not be available depending on the control mode.
• E1-07, E1-08 and E-10 are available only in the V/f control and Open Loop Vector control
modes.
• E1-11, E1-12 and E-13 are available only in the V/f control and Closed Loop Vector control
modes.
V/f
OLV
Sets the motor nameplate full load current in Amps. Automatically set during Auto-Tuning.
V/f
OLV
Sets the motor rated slip. Automatically set during Auto-Tuning.
V/f
OLV
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
V/f
OLV
Sets the number of motor poles. Automatically set during Auto-Tuning.
V/f
OLV
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
V/f
OLV
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
Automatically set during Auto-Tuning.
V/f
OLV
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
OLV
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
OLV
Sets the motor mechanical loss as a percentage of motor rated power (kW).
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Description
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Description
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
CLV
CLV/PM
Setting
Page
Default:
<5>
Min:
<33>
Max: 120.0 Hz
Default:200.0 V
<9>
common_
Min: 0.0 V
TMonly
Max: 255.0 V
<9>
Default:
<5>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<5>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<2> <9>
Min: 0.0 V
Max: 255.0 V
<9>
Default:
<5>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<2> <9>
Min: 0.0 V
Max: 255.0 V
<9>
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
Default: 0.0 V
<9>
Min: 0.0 V
Max: 255.0 V
<9>
Default: 0.0 V
<9> <13>
Min: 0.0 V
Max: 255.0 V
<9>
Setting
Page
Default:
<4>
common_
Min: 10% of drive rated
TMonly
current
Max: 200% of drive
rated current
<10>
common_
Default:
<4>
TMonly
Min: 0.00 Hz
Max: 20.00 Hz
common_
Default:
<4>
TMonly
Min: 0 A
Max: E2-01
<10>
common_
Default: 4
TMonly
Min: 2
Max: 48
common_
Default:
<4>
Min: 0.000 Ω
TMonly
Max: 65.000 Ω
common_
Default:
<4>
TMonly
Min: 0.0%
Max: 40.0%
common_
Default: 0.50
TMonly
Min: 0.00
Max: 0.50
common_
Default: 0.75
TMonly
Min: E2-07
Max: 0.75
common_
Default: 0.0%
TMonly
Min: 0.0%
Max: 10.0%
169
169
169
169
169
169
169
169
169
169
170
170
171
171
171
171
171
171
172

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents