Setting 4: Elevator units 1 (speed in m/s, accel/decel rate and jerk in s)
Setting 5: Elevator units 2 (speed in m/s, accel/decel rate in m/s
Setting 6: Elevator units 3 (speed in ft/min, accel/decel rate in ft/s
o1-04: V/f Pattern Setting Units
Determines the units used for the frequency reference when setting parameters that create the V/f pattern: E1-04, E1-06,
E1-09, E1-11, and E2-04. For motor 2, this includes parameters E3-04, E3-06, E3-07, E3-09, and E4-04.
Enabled only in vector control modes (CLV and CLV/PM).
No.
o1-04
Setting 0: Hz
Setting 1: r/min
Note:
For motor 2, o1-04 can only be set to 0 for Hertz.
o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency.
No.
o1-10
Note: This parameter is displayed only when the drive is set to allow for user-set units (o1-03 = 3).
o1-11: User-Set Display Units Decimal Display
Determines how many decimal points should be used to set and display the speed reference.
No.
o1-11
Setting 0: No decimal point
Setting 1: One decimal point
Setting 2: Two decimal points
Setting 3: Three decimal points
o1-12: Length Units
Sets the units used to for distance control and for the sheave diameter.
Note: This parameter determines whether the following parameters are set in millimeters or inches: o1-20, S5-11, S5-12, U4-42,
U4-33, and U4-44.
No.
o1-12
0: Millimeter units
1: Inch units
o1-20: Traction Sheave Diameter
WARNING! Make sure that the traction sheave diameter (o1-20), the deceleration distance (S5-11) and the stop distance (S5-12) are
all set to the correct units. If these setting are incorrect, the elevator will not stop at the designated location, overrun will occur, and may
cause serious injury or death. Before using stop distance control, make sure that parameter o1-20, S5-11, and S5-12 are set to the right
values.
Sets the traction sheave diameter.
No.
o1-20
<1> The default setting will change if the length units are set in inches (o1-12 = 1). The setting range will become 3.70 to 78.00 inches, and the
default will be 15.70 inches.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Name
V/f Pattern Setting Units
Name
User-Set Display Units Maximum Value
Name
User-Set Display Units Decimal Display
Name
Length Units
Name
Traction Sheave Diameter
5.10 o: Operator Related Settings
2
3
, jerk in m/s
)
2
, jerk in ft/s
3
)
Setting Range
0 or 1
Setting Range
1 to 60000
Setting Range
0 to 3
Setting Range
0 or 1
Setting Range
100 to 2000 mm
<1>
Default
Determined by A1-02
Default
Determined by o1-03
Default
Determined by o1-03
Default
5
0
Default
400 mm
<1>
225