5.11 S: Elevator Parameters
S4-05: Rescue Operation Torque Limit
Sets a time limit for Light Load Direction Search.
No.
S4-05
S4-06: Rescue Operation Power Supply Selection
Specifies the type of backup power supply the drive should switch to when the power goes out.
No.
S4-06
0: Battery
1: UPS (single-phase)
2: UPS (three-phase)
S4-07: UPS Power
Sets the capacity of the UPS.
No.
S4-07
S4-08: UPS Operation Speed Limit Selection
Determines how a speed limit should be applied to the Rescue Operation speed (d1-25) when operating from a UPS. The
drive calculates the appropriate speed limit based on the UPS capacity set in S4-07. This speed limit helps prevent voltage
saturation and motor stall during Rescue Operation.
No.
S4-08
0: Disabled
1: Enabled until Light Load Direction Search is complete
2: Enabled until stop
S4-12: DC Bus Voltage during Rescue Operation
Sets the DC bus voltage during Rescue Operation.
No.
S4-12
S4-13: Rescue Operation Power Supply Deterioration Detection Level
Determines at which level of backup power supply deterioration a PF5 fault is triggered. The following conditions will
trigger PF5:
• During Rescue Operation, DC bus voltage < [S4-12 × (S4-13 - 10%)]
• 100 ms after Rescue Operation has been triggered, the DC bus voltage does not rise above S4-12 × S4-13 before the
motor starts
No.
S4-13
238
Parameter Name
Rescue Operation Torque Limit
Parameter Name
Rescue Operation Power Supply Selection
Parameter Name
UPS Power
Parameter Name
UPS Operation Speed Limit Selection
Parameter Name
DC Bus Voltage during Rescue Operation
Parameter Name
Rescue Operation Power Supply Deterioration Detection Level
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
0 to 300%
Setting Range
0 to 2
Setting Range
0.0 to 100.0 kVA
Setting Range
0 to 2
Setting Range
0 to 800 V
Setting Range
10 to 100%
Default
100%
Default
0
Default
0.0 kVA
Default
2
Default
0 V
Default
80%