YASKAWA L1000A Technical Manual page 105

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Input Value
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Motor Rated Frequency
Number of Motor Poles
Motor Rated Speed
PG Encoder Resolution
(Pulses per Revolution)
Motor No-Load Current
Motor Rated Slip
Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1-
feedback detection.
Type
Motor Data Input
Stationary Auto-Tuning
Stationary Stator Resistance Auto-
Tuning
Rotational Back EMF Constant
Auto-Tuning
Table 4.8
lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.
The information needed is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to page
Input Value
Control Method
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Number of Motor Poles
Motor Rated Speed
Stator 1 Phase Resistance
d-axis Inductance
q-axis Inductance
Voltage Constant
<1>
Voltage Constant
<1>
Encoder Resolution (Pulses per Revolution)
Encoder Offset
<1> Only parameter T2-13 or T2-14 has to be input. Select one and leave the other empty.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Table 4.6 Auto-Tuning Input Data
Input
Unit
Parameter
T1-02
kW
T1-03
Vac
T1-04
A
T1-05
Hz
T1-06
-
T1-07
r/min
T1-08
-
T1-09
A
T1-10
Hz
Table 4.7 Types of Auto-Tuning for Permanent Magnet Motors
Setting
• Use if a motor test report is available
T2-01 = 0
• Input motor data from the motor test report. Convert data into the correct unit before inputting data if necessary.
• Motor does not rotate during Auto-Tuning
• Use if a motor test report is not available
T2-01 = 1
• Input motor data from the motor name plate. Make sure to convert data into the correct units. The drive automatically calculates the
motor data.
• Tunes stator resistance only.
T2-01 = 2
• Should be performed if the motor cabling has changed.
• Use if a motor test is not available
• Tunes the Motor Induction Voltage only
T2-01 = 11
• Should be performed after Motor data are set and the encoder offset is adjusted.
• The motor must be uncoupled from the mechanical system (remove ropes).
102
for details on the tuning mode selection and the tuning process.
Table 4.8 Auto-Tuning Input Data
Input
Parameter
A1-02
T2-04
T2-05
T2-06
T2-08
T2-09
T2-10
T2-11
T2-12
T2-13
mVs/rad (el.)
T2-14
mVmin (mech.)
T2-16
T2-17
deg (mech.)
Tuning Type (T1-01)
0
1
Rotational
Stationary 1
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
, E5-
, and some F1-
Requirements and Benefits
Unit
0
Motor Data input
-
7
kW
Yes
Vac
Yes
A
Yes
-
Yes
r/min
Yes
Ω
Yes
mH
Yes
mH
Yes
Yes
Yes
-
Yes
Yes
4.5 Auto-Tuning
2
Stationary for Line-to-
Stationary 2
Line Resistance
Yes
No
Yes
No
No
No
No
No
No
parameters for speed
Tuning Type (T2-01)
2
1
Stationary Stator
Rotational Back
Stationary
Resistance
7
7
Yes
No
Yes
No
Yes
Yes
Yes
No
Yes
No
No
No
No
No
No
No
No
No
No
No
Yes
No
Yes
No
4
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
11
EMF Constant
4
7
No
No
No
No
No
No
No
No
No
No
No
No
105