Function Block Related Parameters - ABB UMC100-FBP Technical Description

Fieldbusplug
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

Function Block Related Parameters

Aux Input Block
In the standard built-in applications the inputs of this function block are connected to the digital inputs of
the DX1xx module (see section 'Using Expansion Modules').
Param-
eter
Number
51 - 56
57 - 61
63/64
65/66
67/68
69/70
71/7
73/74
75 - 80
UMC100-FBP
Parameter Name
Description, Explanation
Aux inp 1-6 ack
Deinition of the fault reset
mode
behavior
Aux Inp 1-6 reac-
Deinition of the input
tion
function
NC: Normally closed
NO: Normally open
Aux Inp 1-6 mes-
Message text line 1 and
sage Line 1/Line 
line 
Aux Inp 1-6 delay
Input delay time in mul-
tiples of 100ms
Options
Manual Reset (0)
Auto Reset (1)
Disabled (0)
Fault (NC) Motor in On/Off (1)
Fault (NO) Motor in On/Off ()
Fault (NC) Motor in On (3)
Fault (NO) Motor in On (4)
Warning (NC) Motor in On/Off (5)
Warning (NO) Motor in On/Off (6)
Warning (NC) Motor in On (7)
Warning (NO) Motor in On (8)
Free text with 8 characters
for each line. Default: „Aux
DIx" with x=1...6
0 ... 55 in multiples of 0.1s
Example: A value of 5 means
500ms
- 114 -
V 6
Adjustable
via
All
All
DTM,
UMC100-
PAN
All exclud-
ing GSD-
PDQ
FieldBusPlug / Issue: 11.009