BONFIGLIOLI Active cube Operation Manual page 81

Hide thumbs Also See for Active cube:
Table of Contents

Advertisement

Bit 4:rfg enable
Rfg enable = 0 The reference speed comes from a manufacturer-specific special
Rfg enable = 1 The reference speed corresponds to the ramp output.
The special function will only be evaluated if 1299
not "9-zero".
If 1299
S. Special Function Generator
always be used.
Bit 5:rfg unlock
Rfg unlock = 0 The last speed will be maintained and used.
Rfg unlock = 1 The ramp function is active and changes according to the reference
value and the ramp.
Bit 6/rfg use ref
Rfg use ref = 0 Reference value "0" is used.
Rfg use ref = 1 The reference value from
used.
Bit 8 HALT
HALT = 0
HALT = 1
If 1299
S. Special Function Generator
output will also be used if bit 4 "rfg enable" = 1, and if bit 4 "rfg enable" = 0, the
reference value from the source specified in 1299
Bit 4 rfg enable = 0
Bit 4 rfg enable = 1
10/13
function.
= "9-Zero", the value of the ramp output will
 Execute positioning.
 Stop axis. (The frequency inverter remains enabled in "Operation
enabled" state.)
≠ "9-Zero", the reference value from the ramp
Reference value source
1299
S. Special Function Gen-
≠ "9-Zero"
erator
Reference value from special
function
Reference value from ramp
output
ACU
Modbus/TCP
S. Special Function Generator
Override Target Velocity vl [rpm]
S. Special Function Generator
1299
S. Special Function
Generator
Reference value from ramp
output
is
1459 is
.
= "9-Zero"
79