9.2.4

Function code 101 (=0x65), write 32-bit parameter

Example 1:
Writing of parameter
Rated Frequency
1.
The Rated Frequency is to be set to 10.00 Hz. Parameter
es. Thus the value to be sent is 1000 = 0x03E8.
Request: Master  frequency inverter
MBAP
Field:
Transaction ID
Hex
nn
nn
Response: Frequency inverter  Master
MBAP
Field:
Transaction ID
Hex
nn
nn
The response is the reflected signal of the request message.
Example 2:
Writing of non-permissible value 9.00 Hz in parameter
inverter with address 1.
Parameter
Rated Frequency
Request: Master  frequency inverter
MBAP
Field:
Transaction ID
Hex
nn
nn
Error response: Frequency inverter  Master
MBAP
Field:
Transaction ID Protocol ID Length
Hex
nn
nn
The sent exception condition code is the hexadecimal value 0x04 = ERROR SLAVE DEVICE.
50
375 (0x0177) in dataset 2 of frequency inverter with address
Unit
ID
Protocol
Length
ID
nn
nn
00
08
01
Unit
ID
Protocol
Length
ID
nn
nn
00
08
01
375 has 2 decimal places. Thus the value to be sent is 900 = 0x0384.
Unit
ID
Protocol
Length
ID
nn
nn
00
08
01
Unit ID
nn
nn
00 03
ACU
Modbus/TCP
Rated Frequency
Func.
DSet/
Par. value
Par.No.
65
21
77
00
Func.
DSet/
Par. value
Par.No.
65
21
77
00
375 in dataset 2 of frequency
Rated Frequency
Func.
DSet/
Par. value
Par.No.
65
21
77
00
Func.
Excep.
01
E5
04
375 has two decimal plac-
00
03
E8
00
03
E8
00
03
84
10/13