6.3
Operating behavior in the case of a communication error
The operating behavior in the case of errors in Modbus/TCP communication can be parameterized.
The required behavior can be set via parameter
Bus Error Behaviour
0 - no response
1 - Error
2 - Stop
3 - Quick stop
4 - Shutdown + Error
5 - Quick stop + Error
The parameter settings
parameter
Local/Remote
For evaluation of settings 2...5, parameter
Control via statemachine".
10/13
Bus Error Behaviour
388
Operating point is maintained.
"Fault" status will be activated immediately. Factory setting.
Control command "Disable voltage" and switch to "switch on disa-
bled" status.
Control command "Quick stop" and switch to "switch on disabled"
status.
Control command "Disable operation" and switch to "Error" status
once the drive has been shut down.
Control command "Quick stop" and switch to "Error" status once
the drive has been shut down.
Bus Error Behaviour
412.
ACU
Modbus/TCP
388.
Function
388 = 2...5 are evaluated depending on
412 must be set to value "1 -
Local/Remote
25