9.2.2
Function code 16, write 32-bit parameter
Example 1:
Writing of parameter
Fixed Frequency 3
cy inverter with address 1.
The fixed frequency is to be set to 44.50 Hz. Parameter
places. Thus the value to be sent is 4450 = 0x00001162.
Request: Master frequency inverter
MBAP
Field:
Transaction ID Protocol ID Length
Hex
nn
nn
Response: Frequency inverter Master
MBAP
Field:
Transaction ID Protocol ID Length
Hex
nn
nn
The response contains the number of written registers
Example 2:
Writing of parameter
Fixed Frequency 3
cy inverter with address 1.
The frequency is to be set to 2000.00 Hz (non-permissible value). Parameter
has two decimal places. Thus the value to be sent is 20000 = 0x00030D40.
Request: Master frequency inverter
MBAP
Field:
Transaction ID Protocol ID Length
Hex
nn
nn
Error response: Frequency inverter Master
MBAP
Field:
Transaction ID Protocol ID Length
Hex
nn
nn
The sent exception condition code is the hexadecimal value 0x04 = ERROR SLAVE DEVICE.
48
482 (0x01E2) in dataset 9 (= RAM for dataset 4) of frequen-
Unit
ID
nn
nn
00 0B
01
Unit
ID
nn
nn
00 0B
01
482 (0x01E2) in dataset 9 (= RAM for dataset 4) of frequen-
Unit
ID
nn
nn
00 0B
01
Unit
ID
nn
nn
00 03
01
ACU
Modbus/TCP
Fixed Frequency 3
Func. DSet/
No.
Par.No.
regis-
ters
10
91 E2
00
02
Func. DSet/
No.
Par.No.
regis-
ters
10
91 E2
00
02
Func.
DSet/
No.
Par.No.
regis-
ters
10
91 E2
00
02
Func.
Ex-
cep.
90
04
482 has two decimal
No.
Par. value
Byte
04
00 00 11 62
482
Fixed Frequency 3
No.
Par. value
Byte
04
00 03 0D 40
10/13