184
Value
LSB:
Note: This Mode will not work correctly when the
data format is32-bit float
Change State by Time:
4. In the Read address frame, select the Device type from the drop down menu, and then specify
PLC register and type that the part continuously reads. Select the data format.
5. In the Write address frame, select the PLC register address that the part writes to when
pressed. Select the data format.
6. In the Attribute frame, select how you want the MultiState Switch object to operate:
Switch Style
Option
JOG+
No. of states:
JOG-
No. of states:
1010-1007, Rev 05
The state of the object is the value in the specified Read Address.
The state of the object is determined by the first bit that is set in the
value specified by the Read Address:
00000000
00000001
00000010
00000100
10000000
If more than one bit is set, the lowest-order bit is used:
00000011
10001000
The state of the object increments automatically at the interval
specified by Time Interval. After the last state, the word lamp reverts to
state 0
Description
Increments the PLC register by 1 each time the key is pressed. When the highest state is
reached, the key resets to State 0.
Range: 1 to 255
Decrements the PLC register by 1 each time the key is pressed. When the State 0 is
reached, the key resets to the highest state.
Range: 1 to 255
Sil ver Plus Se ries In stal la tion & Op er a tion Man ual
state 0
state 1
state 2
state 3
state 8
state 1
state 4