4. Select the data format.
5. In the Attribute frame, select how you want the Set Word object to operate:
Write Constant Value
I
ncrement Value (JOG+)
Decrement Value (JOG-)
Press and Hold Increment
(JOG++)
Press and Hold Decrement
(JOG—)
Periodic JOG++
Automatic JOG—
Periodic Bounce
Periodic Step Up
Periodic Step Down
Set When Window Opens
Set When Window Closes
Set When Backlight On
Set When Backlight Off
6. Refer to the Bit Lamp Object section for information on using the Shape tab. Note that it is
not required to use a shape or a bitmap. In some modes such as Set at window open or
Periodical JOG++ you may prefer to place the part on the window without a shape or bitmap
tied to it.
7. Refer to the Bit Lamp Object section for information on using the Label tab.
8. Click OK. The New Set Word Object dialog closes and the main screen of EasyBuilder
appears with the cursor tied to a rectangular outline of the part you just created at the upper
left corner of the screen. Move the part to the desired location on the window.
9. Once the part is placed onto the window, you can adjust the location of the label inside the
part by clicking once on the label. This will highlight the entire object. Click on the label
again. Now only the label is highlighted, allowing you to move it without moving the part.
Note: if you double-click (click twice rapidly) then you will not highlight the label but rather
enter the Set Word Object's Attribute dialog box.

The Slider Object

The slider object is used to write data to a PLC Register. It also reflects the value in the PLC register. Data is written
to the register when the slider is released. The following data formats are supported:
• 16-bit BCD
• 32-bit BCD
• 16-bit Unsigned
• 16-bit Signed
• 32-bit Unsigned
1010-1007, Rev 05
When touched, sets the Write Address to the specified value.
Each time it is touched, increments the value in the Write Address by the value specified by Inc.
Value, up to the value specified by Upper Limit.
Each time it is touched, decrements the value in the Write Address by the value specified by Dec.
Value, down to the value specified by Bottom Limit.
When touched, increments the value in the Write Address by the value specified by Inc. Value, up
to the value specified by Upper Limit. When held for the time specified by Jog Delay, continues to
increment the value in the Write Address, at the rate specified by Jog Speed.
When touched, decrements the value in the Write Address by the value specified by Dec. Value,
down to the value specified by Bottom Limit. When held for the time specified by Jog Delay,
continues to decrement the value in the Write Address, at the rate specified by Jog Speed.
Increments the value in the Write Address by the value specified by Inc. Value, up to the value
specified by Upper Limit, at the rate indicated by Time Interval.
Decrements the value in the Write Address by the value specified by Dec. Value, down to the
value specified by Bottom Limit, at the rate indicated by Time Interval.
Similar to Periodic Jog++, except that the value begins decrementing when it reaches the Upper
Limit. Then, the value begins incrementing again.
Starting with the value in the Low Limit box, increments the value in the specified register by 1,
until the value in the High Limit box is reached, at the rate specified by the Time Interval. When
the High Limit is reached, the register value is reset to the Low Limit, and the incrementing
repeats.
Starting with the value in the High Limit box, decrements the value in the specified register by 1,
until the value in the Low Limit box is reached, at the rate specified by the Time Interval. When
the Low Limit is reached, the register value is reset to the High Limit, and the decrementing
repeats.
Sets the Write Address to the value specified by Constant, when the Window containing the
Object is displayed.
Sets the Write Address to the value specified by Constant, when the Window containing the
Object is closed.
Writes the specified value to the Write Address when the Backlight turns on.
Writes the specified value to the Write Address when the Backlight turns off.