Table 15: AC Power System Specifications

Item
Redundancy
Output power (maximum) per
power supply
Output power (maximum) per
system
See Also

AC Power Circuit Breaker Requirements for the MX240 Router

See Also
Copyright © 2019, Juniper Networks, Inc.
Table 14: AC Power Supply Electrical Specifications (continued)
Item
Maximum output power
AC input voltage
AC input line frequency
AC input current rating
Efficiency
NOTE:
This value is at full
load and nominal voltage.
Normal-Capacity–Low
Line
2+2
1027 W
2054 W
Replacing an MX240 AC Normal-Capacity Power Supply on page 311
Replacing an MX240 AC Power Supply Cord on page 314
MX240 AC Power Electrical Safety Guidelines and Warnings
AC Power Circuit Breaker Requirements for the MX240 Router on page 45
We recommend that you use a dedicated customer site circuit breaker rated for
15 A (250 VAC) minimum for each AC power feed, or as required by local code. Doing so
enables you to operate the router in any configuration without upgrading the power
infrastructure.
Replacing an MX240 AC Normal-Capacity Power Supply on page 311
MX240 AC Power Electrical Safety Guidelines and Warnings
Specification
1167 W (low line)
2050 W (high line)
Operating range: 100–240 VAC (nominal)
50 to 60 Hz (nominal)
16 A @ 110 VAC maximum
15.1 A @ 200 VAC maximum
84% (low line)
89% (high line)
Normal-Capacity–High
High-Capacity–Low
Line
Line
1+1
2+2
1590 W
1167 W
1590 W
2334 W
Chapter 1: Overview
High-Capacity–High
Line
1+1
2050 W
2050 W
45