Ac Power Circuit Breaker Requirements For The Mx960 Router - Juniper MX960 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX960:
Table of Contents

Advertisement

1
These values are at full load and nominal voltage.
2
For this configuration, total power for zone 0 is 2935 W. The calculation method for zone 1 is the
same as zone 0.
3
Zone 0 requirement.
4. Calculate thermal output (BTUs). To calculate this, multiply the input power requirement (in watts) by
3.41 as shown in
Table 95 on page
Table 95: Calculating Thermal Output
Power Supply
MX960 AC high-capacity
MX960 DC high-capacity
1
Zone 0 output. The calculation method for zone 1 is the same as for zone 0.
RELATED DOCUMENTATION
Power Requirements for an MX960 Router | 205
Electrical Specifications for the MX960 AC Power Supply | 203
Electrical Specifications for the MX960 DC Power Supply | 225

AC Power Circuit Breaker Requirements for the MX960 Router

The circuit breaker protection on all the power supplies should be designed according to National Electrical
Code (NEC) of country of system installation or any similar local standard based on maximum drawn current
of the power supply specified in this document.
Each normal-capacity AC power supply has a single AC receptacle located in the chassis directly above
the power supply.
Each high-capacity AC power supply have dual feeds. One AC receptacle located on front panel of the
power supply while second one is located on chassis above the power supply.
Each high-capacity second-generation AC power supply has dual feeds. Both AC receptacles are located
on front panel of the power supply.
220.
Thermal Output (BTUs per hour)
3335 * 3.41 = 11,372 BTU/hr
3413 * 3.41 = 11,638 BTU/hr
1
1
220