MX240 5G Universal Routing Platform Hardware Guide
Table 82: Calculating Power Budget
Power Supply
MX240 AC Normal-capacity (low-line)
MX240 AC Normal-capacity (high-line)
MX240 AC High-capacity (low-line)
MX240 AC High-capacity (high-line)
MX240 DC Normal-capacity
MX240 DC High-capacity (DIP=0)
MX240 DC High-capacity (DIP=1)
Table 83: Calculating Input Power Examples
Power Supply
MX240 AC Normal-capacity (high-line)
MX240 AC High-capacity (high-line)
MX240 DC Normal-capacity
MX240 DC High-capacity
158
Table 82 on page 158
lists the power supplies, their maximum output power, and
unused power (or a power deficit). See
for the MX240 Router" on page 51
the MX240 Router" on page 44
electrical specifications.
1
For this configuration, output power excluding the cooling system is 1400 W.
Calculate input power. In this step, the input power requirements for the example
3.
configuration are calculated. To do this, divide the total output requirement by the
efficiency of the power supply as shown in
1
These values are at full load and nominal voltage.
2
For this configuration, total power is 1485 W.
Calculate thermal output (BTUs). To calculate this, multiply the input power
4.
requirement (in watts) by 3.41. See
"DC Power Supply Electrical Specifications
and
"AC Power Supply Electrical Specifications for
for more information about the MX240 power supply
Maximum System Output
Power
2054 W
1590 W
2334 W
2050 W
1600 W
2400 W
2600 W
Table 83 on page
1
Power Supply Efficiency
85 %
89 %
~98 %
~98 %
Table 84 on page
1
Unused Power
654 W
190 W
934 W
650 W
200 W
1000 W
1200 W
158.
Input Power Requirement
1747 W
1669 W
1515 W
1515 W
159.
Copyright © 2019, Juniper Networks, Inc.
2