15
TROUBLESHOOTING
Related buffer memory
Error
address
code
Axis/
Axis/
(decimal)
CH 1
CH 2
26
126
914
27
127
28
128
915
29
129
923
13
113
924
34
134
925
Setting range
Axis/
CH 3
226
Creep speed
Pr.14
227
1 to 100000 (pulse/s)
228
ACC/DEC time at OPR
Pr.15
229
1 to 5000 (ms)
Current feed value,
Pr.9
count value simultaneous
change function selection
0: Values not changed
simultaneously
1: Count value changed
213
together at currnt value change
2: Current feed value changed
together at preset
3: Values changed both at
current value change and at
preset
Coincidence detection
Pr.18
setting
0: Coincidence detection not
234
request
1: Coincidence detection
requested
Remedy
Set the value within the setting range and lower than the
"
OPR speed", and turn OFF and then ON the
Pr.13
programmable controller CPU READY signal (Y0).
Set the value within the setting range and turn OFF and then
ON the programmable controller CPU READY signal (Y0).
Set the "
Coincidence detection setting" to "0:
Pr.18
Coincidence detection not request", and turn OFF and then
ON the programmable controller CPU READY signal (Y0).
Set liner counter for the counter format. (Refer to Section 5.6)
15.2 Error and Warning Descriptions
15.2.1 Error code list
9
10
11
12
13
14
15