Mitsubishi MELSEC-Q Series User Manual page 198

Positioning module with built-in counter function
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

10
JOG OPERATION
(3) When the "JOG start signal (YC to Y11)" is turned ON again during
Figure 10.4 Operation when the JOG start signal (YC to Y11) is turned ON during deceleration
(4) When the "axis stop signal (Y4 to Y6)" is turned OFF after a stop caused
Figure 10.5 Operation when the axis stop signal (Y4 to Y6) is turned from ON to OFF with the JOG start signal (YC to Y11) ON
10
- 7
10.3 JOG Operation Example
deceleration caused by turning the "JOG start signal (YC to Y11)" from
ON to OFF
When the "JOG start signal (YC to Y11)" is turned ON again during deceleration
caused by turning the "JOG start signal (YC to Y11)" from ON to OFF, the JOG start
signal (YC to Y11) is ignored.
V
Forward run JOG
ON
start signal
(YC,YE,Y10) or
O
FF
reverse run JOG
start signal
(YD,YF,Y11)
ON
BUSY signal
OFF
(X8 to XA)
by turning ON the "axis stop signal (Y4 to Y6)" with the "JOG start signal
(YC to Y11)" ON
When the "axis stop signal (Y4 to Y6)" is turned OFF after a stop caused by turning
ON the "axis stop signal (Y4 to Y6)" with the "JOG start signal (YC to Y11)" ON, JOG
operation is not performed.
JOG operation can be started by turning the "JOG start signal (YC to Y11)" from OFF
to ON again.
V
Forward run JOG
start signal
ON
(YC,YE,Y10) or
reverse run JOG
OFF
start signal
(YD,YF,Y11)
Axis stop signal
OFF
(Y4 to Y6)
ON
BUSY signal
OFF
(X8 to XA)
JOG operation
The JOG start signal (YC to Y11) is ignored.
JOG is not started even if the axis
ON
stop signal is (Y4 to Y6) turned OFF.
t
t

Advertisement