Mitsubishi MELSEC-Q Series User Manual page 223

Positioning module with built-in counter function
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

12
COUNTER FUNCTION
(b) It takes approx. 150 s from when the QD72P3C3 detects coincidence until it
makes an interrupt request to a programmable controller CPU.
(c) Set the interrupt factors (SI) and interrupt pointers of the programmable controller
CPU on the screen displayed by selecting [PLC parameter] - [PLC system] -
"Intelligent function module setting" - "Interrupt pointer settings".
1) PLC side "Interrupt pointer Start No."
Set the start interrupt pointer number of the programmable controller CPU.
Setting range: 50 to 255
2) CPU side [Interrupt pointer No. of module]
Set the number of interrupt executing conditions set in "interrupt setting".
Setting range: 1 to 16
3) Intelli. module side "Start I/O No."
Set the start I/O number of the intelligent function module for which interrupt
setting has been made.
Setting range: 0000 to 0FF0 (
4) Intelli. module side "Start SI No."
Set the interrupt pointer number of intelligent function module set to "interrupt
(SI) No." in interrupt setting.
Setting range: 0 to 15
The following shows a setting example where SI 0 to 2 of the QD72P3C3 in the
slot of start I/O No. 20 are assigned to interrupt pointers I50 to I55.
)
H
12.5 Coincidence Detection Function
9
10
11
12
13
14
15
12
- 9