Vsm Drive-Cliq (Cu): Alternating Cyclic Data Transfer Error; Vsm Drive-Cliq (Cu): Inconsistent Component Properties - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
Fault cause:
32 (= 20 hex):
Error in the telegram header.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
F34895

VSM DRIVE-CLiQ (CU): Alternating cyclic data transfer error

Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the Voltage Sensing Module involved (VSM) to the Control
Unit.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
F34896

VSM DRIVE-CLiQ (CU): Inconsistent component properties

Message value:
Component number: %1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The properties of the DRIVE-CLiQ component (Voltage Sensing Module), specified by the fault value, have changed
in an incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ
cable or DRIVE-CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy:
- carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be
used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the
original cables should be used (ensure compliance with the maximum cable length).