4 Faults and alarms
4.2 List of faults and alarms
F60044 (N, A)

Parallel interface node failure

Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A fault involving the parallel connection of power units has occurred.
Fault value (r0949, interpret decimal):
1: There is a fault on one of the slaves.
2: One of the slaves is not in the Operation state (e.g. because its enable signal is at "0")
3: There are fewer power units connected in parallel that are active than set using p51802.
4: There are fewer devices that are active than set using p51815.
50: The switchover to power unit topology 2 is not possible, as this SINAMICS DCM is not equipped with option S50.
51: The switchover to power unit topology 2 is not permissible for "n+m" operation.
52: The parallel switching master in power unit topology 2 is not the same as in power unit topology 1.
53: The feedback indicating the active power unit topology does not match the selected power unit topology.
Remedy:
- Check the slave with fault.
- Check the enable signal of the slaves
- Check the setting for the minimum number of devices (p51802, p51815).
- Check the parameterization of the switchover of the power unit topology.
See also: p51802 (Parallel interface number of power units)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60045 (N, A)

Standstill field not permitted in operation

Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The standstill field was activated while the drive was operational.
The binector input p50692 to activate the standstill field must not have a 1 signal in operation.
See also: p50692 (Cl-loop field curr ctrl sig source for inject of standst field)
Remedy:
If required, set binary input p50692 - used to activate the standstill field - to a 0 signal.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60046 (N, A)

Wire break at "Main setpoint" analog input

Message value:
-
Message class:
General drive fault (19)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A wire break has been detected at the CUD's "Main setpoint" analog input (X177.25/26).
This fault is triggered if p50700 = 2 (unipolar monitoring of current input (+4 mA to +20 mA)) is set and an input
current of less than 2 mA is flowing.
Possible fault causes:
- Wire break or contact problem on supply line
- Parameter p50700 set incorrectly
1150