Remedy:
In the case of CBE20 SINAMICS Link:
Correct the parameter assignment.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A50005 (F)

COMM BOARD: Alarm 5

Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
CBE20 SINAMICS Link:
Sender not found on SINAMICS Link.
Alarm value (r2124, interpret decimal):
Address of sender that cannot be located
See also: p8872 (SINAMICS Link address receive PZD)
Remedy:
CBE20 SINAMICS Link:
Check the connection to the sender.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A50006 (F)

COMM BOARD: Alarm 6

Message value:
Info. 1: %1, info. 2: %2
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
CBE20 SINAMICS Link:
The parameter assignment indicates that the sender and the receiver are one and the same. This is not permitted.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = Drive object number from p8872
Info. 2 (decimal) = Index from p8872
See also: p8836 (SINAMICS Link address), p8872 (SINAMICS Link address receive PZD)
Remedy:
In the case of CBE20 SINAMICS Link:
Correct the parameter assignment. All p8872[index] must be set to a value not equal to p8836.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A50010 (F)

PN/COMM BOARD: Station name invalid

Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
CBE20:
PROFINET Name of Station is invalid.
Remedy:
CBE20:
Correct the name of the station (p8940) and activate (p8945 = 2).
See also: p8940 (CBE2x Name of Station)
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms