5.3.5

Setting devices (except for annunciators) (SET)

SET
SET
Function
(1) When the execution command is turned ON, the status of the designated devices becomes
as shown below:
Bit device
When Bit Designation has been Made for Word Device
(2) Devices turned ON by the instruction remain ON when the same command is turned OFF.
Devices turned ON by the SET instruction can be turned OFF by the RST instruction.
X5
X7
(3) When the execution command is OFF, the status of devices does not change.
Command
: Bit device number to be set (ON)/Word device bit designation (bits)
D
Internal Devices
Set
Data
Bit
Word
D
(Except
T, C)
Device
Command
SET
Y10
RST
Y10
Command
Constants
Others
––
Device Status
Coils and contacts turned ON
Designation bit set at 1
ON
X5 OFF
X7 OFF
ON
Y10 OFF
5.3.5 Setting devices (except for annunciators) (SET)
SET
SET
D
ON
5.3 Output Instruction