SmartPAC 2 with WPC Integration

Anti-repeat Test

!
DANGER
INJURY DURING TESTING
Keep all personnel away from the press during testing.
Ensure that there is no die or other tooling in the press during testing.
Failure to comply with these instructions will result in death or serious injury.
DANGER
!
OPERATOR STATION MAY NOT MEET SAFETY REQUIREMENTS
Ensure that the operator station is wired correctly.
Ensure that on any non-Wintriss operator station run buttons are placed so that two hands
are required to push both buttons at the same time and no one can press both buttons with
one hand or with one hand and one elbow or in any other way.
Ensure that on any non-Wintriss operator station the run buttons have guard rings or other
means in place to prevent unintentional operation.
Failure to comply with these instructions will result in death or serious injury.
Perform the following test to verify that the press will cycle only once in Single Stroke when
you press both run buttons simultaneously.
1. Set the STROKE SELECT switch to SINGLE STROKE.
2. Press and hold down both run buttons while the press cycles and continue to hold them
down for ten seconds after the press stops. The press should make only one stroke
(cycle) and then top stop. It should not make any more strokes while you hold down the
run buttons.
• If the press makes one stroke (cycle) and then stops, it is operating correctly. Go to
the next applicable test.
• If the press does cycle again after making one stroke, check the wiring. Repeat the
test in step 2. If the press still cycles again after it makes one stroke, stop! Turn off
the press. Contact Wintriss Tech Support.
Installing SmartPAC 2 and WPC
Chapter 2
1126800
page 139