13.2.3 Error code list [BFM #29 (X-axis), BFM #129 (Y-axis)]

When an error occurs
Error
Error category
Code
(decimal)
-
Setting error
3000
3001
3002
Control errors
3004
3005
3006
an error code is stored in decimal to BFM #29 (X-axis) and BFM #129 (Y-axis).
,
Error Content
0
No error
Incorrect value range
2
A value outside of the setting range is set to the
buffer memory.
Value overflow
3
The converted pulse data (e.g. travel distance or
operation speed) exceeds 32 bits.
The operation pattern has Multiple operation
5
patterns
Center coordinate setting error
When one of the following applies:
-
Start point = center coordinate
6
-
End point = center coordinate
-
Center coordinate is outside of the
-2,147,483,648 to 2,147,483,647 PLS range
Table operation start No. error
The table No. is executed outside of the range 0 to
299.
Jump No. fault
The jump No. for the table information is set outside
the range 0 to 299.
Command format fault
The operation information of the table information is
set by a non-defined number.
Current value overflow at absolute value detection
system
The converted pulse data of the current address
exceeds 32 bits.
Manual pulse generator input error
Interpolation error during ring operation
Linear interpolation, linear interpolation (interrupt
stop) or circular interpolation is performed while the
ring operation is set.
13.2 Check Error Code
Action
-
Change the setting value in buffer memory so that it
is within the setting range.
Change the setting value of the corresponding buffer
memory so that the converted pulse data is smaller
than 32-bit data.
Change the program in the PLC main unit so that
only one operation pattern is selected.
Check the center coordinate setting and set so that a
circle is formed.
Change the table operation start No. to 0 to 299.
Change the jump No. for the table information to 0 to
299.
Change the operation information of the table
information.
Turn the power OFF, or perform a mechanical zero
return or data set type zero return.
Change the pulse generator input (numerator) and
pulse generator input (denominator) settings.
Reset the ring operation setting before executing the
interpolation.
13 Diagnostics
11
12
13
A
B
271