Mitsubishi FX3U-20SSC-H User Manual page 133

Hide thumbs Also See for FX3U-20SSC-H:
Table of Contents

Advertisement

FX
-20SSC-H Positioning Block User's Manual
3U
3) When the version is Ver.1.30 or later "interrupt 1-speed constant quantity feed (constant position stop
mode) shortest allowable stop" is enabled. (Refer to Fig. B.)
If the system cannot stop at the target position (target address 1) with the setting value of deceleration
time, it stops at the target position (target address 1) using a deceleration time
automatically. (Refer to Fig. B.)
However, if the travel distance to the target position (target address 1) after the interrupt input (INT0)
turns ON is shorter than the travel distance required for a sudden stop, the system passes the 1st target
position (target address 1), decelerates, and then stops at the 2nd target position (target address 1).
(Refer to Fig. C.)
Start
Figure B
*1.
Deceleration time setting value is automatically set between sudden stop deceleration time and
deceleration time.
Target address 1
Operation speed 1
Acceleration/deceleration
time change command
(Ver.1.30 or later)
Mode selection for the
Interrupt 1-speed
constant quantity feed
Interrupt 1-speed
Constant Quantity Feed
(Constant position stop
mode) shortest allowable
stop (Ver.1.30 or later)
X-INT0 (input terminal)
Y-INT0 (input terminal)
Maximum speed
Acceleration time
Deceleration time
Acceleration/deceleration
*2
mode
Ring counter setting
(Ver.1.10 or later)
Sudden stop deceleration time (Ver.1.20 or later)
Acceleration time 2 (Ver.1.30 or later)
Deceleration time 2 (Ver.1.30 or later)
*2.
Set approximate S-shaped acceleration/deceleration or trapezoidal acceleration/deceleration in
"acceleration/deceleration mode."
Interrupt input (INT0)=ON
Travel distance
required for
sudden stop
Travel distance
required for
deceleration stop
Start
Target address 1
BFM #501,#500
BFM #503,#502
Operation command 2
BFM #519 b5
Operation command 2
BFM #519 b6
Operation command 2
BFM #519 b7
BFM #14009,#14008
BFM #14018
BFM #14020
Operation parameter 1 BFM #14000 b11
Operation parameter 2 BFM #14002 b3
BFM #14102
BFM #14108
BFM #14110
7 Before Starting Positioning Operation
7.11 Cautions for Positioning Operation
→ For sudden stop, refer to Section 7.5
Interrupt input (INT0)=ON
Figure C
BFM Number
X-axis
Y-axis
BFM #601,#600
BFM #603,#602
BFM #619 b5
BFM #619 b6
BFM #619 b7
-
-
-
-
BFM #14209,#14208
BFM #14218
BFM #14220
BFM #14200 b11
BFM #14202 b3
BFM #14302
BFM #14308
BFM #14310
*1
set by the 20-SSC-H
Target address 1
Travel distance
required for
sudden stop
Travel distance
required for
deceleration stop
Data type
Control data
Control data
Control data
Control data
Control data
Input terminal
Input terminal
Positioning parameters
Positioning parameters
Positioning parameters
Positioning parameters
Positioning parameters
Positioning parameters
Positioning parameters
Positioning parameters
127
1
2
3
4
5
6
7
8
9
10