Maintenance Space Guidelines
The maintenance area for the rackmounted Sun Server X4-2 must have the required
access space. The following table lists the maintenance access requirements for the
Sun Server X4-2 when installed in a rack.
TABLE:
Location
Rear maintenance
Top maintenance
Front maintenance
Electrical Power Requirements
The server uses AC power. The following table lists the power supply specifications
for the Sun Server X4-2.
Note – The power dissipation numbers listed in the following table are the
maximum rated power numbers for the power supply used in the system. The
numbers are not a rating of the actual power consumption of the system. For
up-to-date information about the power consumption, go to Oracle's Sun Power
Calculators web site and click on the Sun Server X4-2 link:
http://www.oracle.com/us/products/servers-storage/sun-power-calc
ulators/index.html
TABLE:
Parameter
Voltage (nominal)
Input current (maximum)
Frequency (nominal)
The Sun Server X4-2 can operate effectively over a range of voltages and frequencies.
However, it must have a reliable power source. Damage to the server might occur if
the ranges are exceeded. Electrical disturbances such as the following might damage
the system:
8
Sun Server X4-2 Installation Guide • February 2014
Maintenance Access Requirements
Maintenance Access Requirement
91.4 cm (36 inches)
91.4 cm (36 inches)
123.2 cm (48.5 inches)
Power Supply Specifications
Specification
100 to 127/200 to 240 VAC
7.2 A @ 100-127 VAC; 3.4 A @ 200-240 VAC
50/60 Hz (47 to 63 Hz range)