Figure 11 Secure Anti-Tip Brackets To The Floor - Oracle Pillar Axiom 600 Hardware Installation Manual

Oracle pillar axiom 600 hardware installation guide
Table of Contents

Advertisement

Chapter 2 Set Up the Rack
3 Position the anti-tip bracket so that it points away from the rack and is
parallel to the sides.
4 Adjust the anchor bolt so that it is finger-tight against the anti-tip bracket,
and secure the anti-tip bracket to the floor.

Figure 11 Secure anti-tip brackets to the floor

5 Repeat Step 1 through Step 4 for all four corners.
About Stabilizer Plate Installation
At the front of the rack, you can install an optional stabilizer plate instead of anti-
tip brackets. Stabilizer plates provide greater stability than anti-tip brackets,
which must be removed in order to install a stabilizer plate. You cannot use anti-
tip brackets in a bay because the anchor bolts are used to hold the baying plates
in place. Therefore you should use stabilizer plates for racks in a bay.
Also note that if you have removable floor panels, you must bolt the stabilizer
plates through to the solid sub-floor.
Install a Stabilizer Plate (Optional)
Use stabilizer plates to provide greater stability than anti-tip brackets for the Pillar
Axiom 600 system.
1 Place the stabilizer plate at the front of the rack with the short side up.