Pallet Double Stacking; Floor Requirements; Weight; Floor Slope - Oracle StorageTek SL3000 Manual

Modular library system
Hide thumbs Also See for StorageTek SL3000:
Table of Contents

Advertisement

Installation Site Requirements

Pallet Double Stacking

In the event that a forklift is unavailable to safely remove the module, notify the
installation coordinator. Inform them that the library may need to be picked up from
the site by the delivery company, taken off the second pallet, and re-delivered.
Delivery personnel are not authorized to remove the modules from the second pallet
without proper equipment.

Floor Requirements

You can install the SL3000 library on a raised, solid, or carpeted floor with a smooth
surface, as long as there is adequate airflow. If the floor is raised, ensure there are no
ventilation panels directly below the library. If the floor is solid, you should route
cables from the ceiling to avoid creating a tripping hazard. If the floor is carpeted,
ensure the carpet is approved for computer-room equipment and provides protection
from electrostatic discharge (ESD).

Weight

Verify the site floor can support the weight of the library. It must support 454 kg (1,000
lb) per weight distribution pad. There are four distribution pads per module, and each
measures 4 by 8 inches.
If the equipment must be transported on elevators, the elevator cars must be capable
of safely handling the weight. Depending on the library configuration, the weight of
the library can vary (see

Floor Slope

Robots must travel along a level plane throughout the library. Any excessive
out-of-plane conditions could cause binding, premature wear, and damage to the
robots. Use the height of the weight pads to adjust the library on a sloped floor.

Environmental Requirements

For optimal reliability, maintain the environment between the recommended ranges.
Although this equipment is designed to operate in environmental conditions of 20% to
80% humidity, a recommended industry best practice is to maintain a relative
humidity of 40% to 50%.
Table 2–7
Description
Operating
Storage
Shipping
2-6 StorageTek SL3000 Library Guide
Possible Physical Injury. Only use a forklift operated
WARNING:
by a qualified operator to remove a stacked second pallet. Do not
attempt to tilt or slide the pallet off by hand.
"Physical Dimensions and Weights"

Environmental Specifications

Temperature
15 to 32°C (60 to 90°F)
dry bulb
10 to 40°C (50 to
104°F)
-40 to 60°C (-40 to
140°F)
Relative Humidity
(non-condensing)
Wet Bulb Maximum Maximum Altitude
20% to 80%
29.2°C (84.5°F)
10% to 95%
35.0°C (95.0°F)
10% to 95%
35.0°C (95.0°F)
on page 2-1).
3.05 km (10,000 ft)
3.05 km (10,000 ft)
15.24 km (50,000 ft)

Advertisement

Table of Contents
loading