Chapter 5 Connect Power Cables

Figure 48 Pulizzi TPC2104 outlet amperage limits

Legend
The Pulizzi PC3365 shown in the following figure requires 230/400 VAC WYE three-
phase input power. The output at each outlet is always 230V. This PDU is only
available outside the United States.

Figure 49 Pulizzi PC3365 outlet amperage limits

Legend
Note: The Pulizzi PC3365–3314 (PN: 1475–00097–20) is a three-phase PDU for
domestic configurations. The outlet field is the same, but there are four switches
on the front panel.
PDU Outlet Amperage Limits
1 Front
2 Back
3 Supports 115V, 208V, or 230V
4 Supports 10A
1 Phase X: 16A
2 Phase Y: 16A
3 Phase Z: 16A
4 Each four-outlet group has an 10A limit
5 Supports 10A
6 Supports 10A
7 Supports 10A
8 Supports 16A maximum across all outlets
116