Appendix C Pillar Axiom Hardware Specifications
Table 68 Rack specifications for a Pillar Axiom 600 system (continued)
Criteria
Heat dissipation
Frame thickness
Loaded weight
The center of gravity of a populated Pillar 42U rack is toward the front. The
threshold tilt angle depends on whether the front or back of the rack faces down
the slope:
● Front faces downward: 12° maximum slope.
● Back faces downward: 24° maximum slope.

Figure 69 Maximum tilt angles for stationary Pillar 42U racks

Pillar Rack Hardware Specification
Pillar rack
● 64 outlets (for single phase PDU)
Note: 48 outlets (for three phase
PDUs) with two maximum PDUs
(115/208V 30A for US and
230/400V 16A for EU).
● Horizontal mount
● Pillar Axiom 600 systems:
28,500BTU/hr
N/A
● Pillar Axiom 600 systems: 1505
pounds (683 kilograms)
Non-Pillar rack (minimum
requirements)
● Pillar Axiom 600 systems:
28,500BTU/hr
12 gauge to 14 gauge
● Pillar Axiom 600 systems:
1505 pounds (683 kilograms)
210