Appendix C Pillar Axiom Hardware Specifications

Pillar Axiom 600 PDU Hardware Specification

If you install non-Pillar PDUs, they must meet the Pillar Axiom 600 PDU
specification, as outlined below.
When you intend to use non-Pillar PDUs, check first with your Pillar Account
Representative to ensure you do not jeopardize your system warranty by
installing the non-Pillar PDUs.

Table 67 PDU specifications

Criteria
Form factor
Receptacles
IEC 60320
Inlet cable
Voltage input
Voltage
output
Pillar Axiom 600 PDU Hardware Specification
20A single-phase
EIA Rack
Mountable
Height: 1U, or
1.75 inches
(4.45 centimeters)
Depth: < 8 inches
(20.3 centimeters)
C13, 12
receptacles
minimum.
Mounted on rear
of chassis
(opposite circuit
breakers).
15 feet
(4.572 meters)
minimum
Plug options:
L6-20P, L5-20P
IEC 2P+E 16A
100–240VAC
100–240VAC
30A single-phase
EIA Rack
Mountable
Height: 1U, or
1.75 inches
(4.45 centimeters)
Depth: < 8 inches
(20.3 centimeters)
C13, 12
receptacles
minimum. Mounted
on rear of chassis
(opposite circuit
breakers).
15 feet
(4.572 meters)
minimum
Plug options:
L6-30P, L5-30P
IEC 2P+E 32A
100–240VAC
100–240VAC
3-phase
EIA Rack
Mountable
Height: 2U, or
3.5 inches
(8.9 centimeters)
Depth: 9.5 inches
(24.13 centimeters)
C13, 24
receptacles (8 per
phase) minimum.
Mounted on back
of chassis
(opposite circuit
breakers).
15 feet
(4.572 meters)
minimum
NEMA L21-30P
IEC 3P+N+E 16A
6H
120/208VAC,
230/400VAC, both
Wye Configuration
120V 1-phase,
230V 1-phase