Chapter 4 Connect Data Cables

About Cable Connections Between Two Racks

Note: This topic applies only to Pillar Axiom 600 systems.
Be sure the two racks are bayed before you make connections between them.
Route the FC cables directly from one rack to the other through the open sides.
Do not route cables from rack to rack through the raised floor. The cables
supplied are not long enough.
When routing an FC cable from one rack to the other, route the cable through the
plastic chase that is dedicated to FC cables on the right side of the rack (from the
back). The FC chase to use depends on which side the racks join.
Important! Make sure the Fiber Channel (FC) cables do not cross over or get too
close to the power supply cords. Keep them separated to minimize EMI (electro-
magnetic interference).
About Cable Connections Between Two Racks