Chapter 2 Set Up the Rack
2 While adjusting the leveling legs to raise or lower the rack, align the holes in
the short side with the holes in the rack frame.
3 Insert an M8 bolt into each hole in the short side of the stabilizer plate.
4 Use the hex wrench to tightly bolt the stabilizer plate to the rack.

Figure 12 Stabilizer plate attached to the rack base and floor

Legend
5 Secure the stabilizer plate to the floor with bolts and washers that are
appropriate for the type of floor.
Important! The floor bolts must be no smaller than M12 in size.
Rack Position
1 M12 (or larger) floor bolts
2 M8 allen-head bolts