Chapter 5 Connect Power Cables

PDU Outlet Amperage Limits

The number of Pillar Axiom 600 system components you can plug into each Pillar-
supplied power distribution unit (PDU) varies.
The Pulizzi TPC2105 shown in the following figure can use 115V, 208V, or 230V,
30A (32A in Europe) electrical service. The overall amperage limits are 24A and
the they are the same at any input voltage.

Figure 47 Pulizzi TPC2105-1 outlet amperage limits

Legend
The Pulizzi TPC2104 shown in the following figure can use 115V, 208V, or 230V,
20A (16A in Europe) electrical service. The overall amperage limit is 16A
regardless of the input voltage.
PDU Outlet Amperage Limits
1 Front
2 Back
3 Supports 10A
4 Supports 10A
5 Supports 10A
6 Supports 10A
7 Supports 12A
8 Supports 12A
9 Supports 24A maximum across all outlets
115