Figure 51 Sample Power Cabling Scheme With 115V On A Tcp2105-1 Pdu - Oracle Pillar Axiom 600 Hardware Installation Manual

Oracle pillar axiom 600 hardware installation guide
Table of Contents

Advertisement

Chapter 5 Connect Power Cables
to the quad with the Slammer and the Pilot, so that the load for the middle quad
with two Bricks and one Slammer is 8.22A. The load on the right quad with one
Slammer, one Brick, and one Pilot is 5.99A. You can distribute the plugs as
shown in the following figure:

Figure 51 Sample power cabling scheme with 115V on a TCP2105-1 PDU

Legend
Other configurations are possible. Make sure that you do not exceed the rating
for a four-outlet bank or the rating for a set of two banks, which is 12A for this PDU.
Note: Another PDU is still needed for the power cords for the redundant circuit,
which was left out of the above figures for simplicity. The redundant PDU should
be cabled the same way.
About Power Cabling
1 SATA Brick 1: 2.12Adrawn
2 SATA Brick 2: 2.12A drawn
3 SATA Brick 3: 2.12A drawn
4 SATA Brick 4: 2.12A drawn
5 Slammer CU 0: 2.42A drawn
6 Slammer CU 1: 2.42A drawn
7 Pilot: 1.45A drawn
8 No amps. drawn for group
9 Total of 4.24A drawn for group
10 Total of 4.24A drawn for group
11 Total of 6.29A drawn for group
12 Total of 4.24A drawn for group
13 Total of 10.53A drawn for groups
119