Endress+Hauser Proline Promass A 100 PROFINET Operating Instructions Manual page 69

Coriolis flowmeter
Hide thumbs Also See for Proline Promass A 100 PROFINET:

Advertisement

Proline Promass A 100 PROFINET
Parameter
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
Endress+Hauser
10.6.5
Configuring the low flow cut off
The Low flow cut off submenu contains the parameters that must be set in order to
configure the low flow cut off.
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
Parameter overview with brief description
Prerequisite
A process variable is selected
in the Assign process variable
parameter (→  69).
A process variable is selected
in the Assign process variable
parameter (→  69).
A process variable is selected
in the Assign process variable
parameter (→  69).
Description
Select process variable for low
flow cut off.
Enter on value for low flow cut
off.
Enter off value for low flow cut
off.
Enter time frame for signal
suppression (= active pressure
shock suppression).
Commissioning
→  69
→  69
→  69
→  69
Selection / User
Factory setting
entry
• Off
• Mass flow
• Volume flow
• Corrected volume
flow
Positive floating-
Depends on country
point number
and nominal
diameter
0 to 100.0 %
0 to 100 s