System integration
60
Status
GOOD - OK
GOOD - Maintenance
demanded
GOOD - Function check
9.3.4
Factory setting
The slots are already assigned in the automation system for initial commissioning.
Assigned slots
Slot
Factory setting
1
Mass flow
2
Volume flow
3
Corrected volume flow
4
Density
5
Reference density
6
Temperature
7 to 14
–
15
Totalizer 1
16
Totalizer 2
17
Totalizer 3
Coding (hex)
Meaning
0x80
No error has been diagnosed.
0xA8
The measured value is valid.
It is strongly recommended to service the device in the
near future.
0xBC
The measured value is valid.
The measuring instrument is performing an internal
function check. The function check does not have any
noticeable effect on the process.