4 Transmitter
4.4.6.

The individual main menus

4.4.6.1.

Editing main menu of channel 1

An overview is given in Overview of the testo 6381 user menu).
You can perform basic settings for channel 1.
1. In the Measuring Mode press SET, select
Channel 1
One of the following parameters can now be selected using 
or , after which the selection must be confirmed with SET:
Channel 1 Unit
The parameter for this channel is selected.
Edit/select parameter with  or , confirm with
entry with ESC.
Scale minimum for channel 1:
The lower scale limit is edited; Unit as selected above.
Editing the value: Scroll one digit to the right using  and
increase value of digit by 1 using . Confirm with
entry with ESC.
Scale maximum for channel 1
The upper scale limit is edited;
Unit as selected above.
Editing the value: Scroll one digit to the right using  and
increase value of digit by 1 using . Confirm with
entry with ESC.
Signal delay ("Attenuation") for channel 1
The analog signal can be delayed ("Attenuation"); a time
constant is selected for this (1 = no delay; 2-15 = delay in
seconds)
Edit/select parameter with  or , confirm with
entry with ESC.
2. Continue to the main menu with  or  or return to Measuring
Mode with ESC.
4.4.6.2.

Editing Main Menu Channel 2 (if this option is available)

See channel 1.
4.4.6.3.

Editing Main Menu Channel 3 (if this option is available)

See channel 1.
68
with  or  and confirm selection with SET.
Main Menu
SET
or abort
SET
or abort
SET
or abort
SET
or abort