7 Diagnostics and Troubleshooting

This chapter includes maintenance and service guidelines,
status messages, warnings and alarms and basic trouble-
shooting.

7.1 Maintenance and Service

Under normal operating conditions and load profiles, the
adjustable frequency drive is maintenance-free throughout
its designed lifetime. To prevent breakdown, danger, and
damage, examine the adjustable frequency drive at regular
intervals depending on the operating conditions. Replace
worn or damaged parts with original spare parts or
standard parts. For service and support, refer to
www.danfoss.com/contact/sales_and_services/.
CAUTION
Danfoss AUTHORIZED PERSONNEL!
Risk of personal injury or equipment damage. Repair and
service must be carried out by Danfoss authorized
personnel only.

7.2 Status Messages

When the adjustable frequency drive is in status mode,
status messages are generated automatically and appear in
the bottom line of the display (see Figure 7.1).
Status
799RPM
Auto
Remote
Hand
Local
O
1
2
Figure 7.1 Status Display
1 Operation Mode (see Table 7.2)
2 Reference Site (see Table 7.3)
3 Operation Status (see Table 7.4)
Table 7.1 Legend to Figure 7.1
MG33AN22
Instruction Manual
1(1)
7.83A
36.4kW
0.000
53.2%
Ramping
Stop
Running
Jogging
.
.
.
Stand by
3
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
Table 7.2 to Table 7.4 describe the displayed status
messages.
Off
The adjustable frequency drive does not react
to any control signal until [Auto On] or [Hand
On] is pressed.
Auto On
The adjustable frequency drive is controlled
from the control terminals and/or the serial
communication.
The adjustable frequency drive is controlled
by the navigation keys on the LCP. Stop
commands, reset, reversing, DC brake, and
other signals applied to the control terminals
will override local control.
Table 7.2 Operation Mode
Remote
The speed reference is given from external
signals, serial communication, or internal
preset references.
Local
The adjustable frequency drive uses [Hand On]
control or reference values from the LCP.
Table 7.3 Reference Site
AC Brake
AC Brake was selected in 2-10 Brake Function.
The AC brake overmagnetizes the motor to
achieve a controlled slow-down.
AMA finish OK
Automatic motor adaptation (AMA) was
carried out successfully.
AMA ready
AMA is ready to start. Press [Hand On] to start.
AMA running
AMA process is in progress.
Braking
The brake chopper is in operation. Generative
energy is absorbed by the brake resistor.
Braking max.
The brake chopper is in operation. The power
limit for the brake resistor defined in
2-12 Brake Power Limit (kW) has been reached.
Coast
Coast inverse was selected as a function
for a digital input (parameter group 5-1*
Digital Inputs). The corresponding terminal
is not connected.
Coast activated by serial communication
7
7
37