Bypass And Drive Control I/O Connections - YASKAWA Z1000U Technical Manual

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

3.6

Bypass and Drive Control I/O Connections

u
Terminals A1, A2, and A3 Input Signal Selection
Terminals A1, A2, and A3 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as
explained in
Table
3.12. Set parameters H3-01, H3-05, and H3-09 accordingly as shown in
and Jumpers on the Terminal Board on page 72
Note:
If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Figure 3.35 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input
Setting
V (top position)
I (bottom position)
No.
Parameter Name
H3-01
Terminal A1 signal level selection
H3-05
Terminal A3 signal level selection
H3-09
Terminal A2 signal level selection
u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
as explained in
Table
3.14. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
72
for locating jumper S5.
Terminal
Terminal AM
Terminal FM
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
for locating jumper S1.
Jumper S1
A1 A2 A3
Table 3.12 Jumper S1 Settings
Voltage input (-10 to +10 V or 0 to 10 V)
Current input (4 to 20 mA or 0 to 20 mA)
Table 3.13 Voltage/Current Selection Parameter Details
Selects the signal level for terminal A1.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
Selects the signal level for terminal A3.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
Refer to Switches and Jumpers on the Terminal Board on page
Table 3.14 Jumper S5 Settings
Voltage Output
V
I
FM
AM
V
I
FM
AM
3.6 Bypass and Drive Control I/O Connections
Table
V
I
Description
Description
Current Output
3.13.
Refer to Switches
Setting
Default
Range
Setting
0 to 3
0
0 to 3
0
0 to 3
2
V
I
FM
AM
V
I
FM
AM
73