YASKAWA Z1000U Technical Manual page 299

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

u
H5: MEMOBUS/Modbus Serial Communication
No.
(Addr.
Name
Hex)
H5-09
CE Detection Time
(0435)
Communications
H5-11
ENTER Function
(043C)
Selection
H5-12
Run Command Method
(043D)
Selection
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Sets the time required to detect a communications error.
CE Detect Time
Adjustment may be needed when networking several drives.
0: Drive requires an Enter command before accepting any
Enter CommandSel
changes to parameter settings.
0: Enter Required
1: Parameter changes are activated immediately without the
1: No EnterRequired
Enter command.
Run CommandSel
0: FWD Run &REV
0: FWD/Stop, REV/Stop
Run
1: Run/Stop, FWD/REV
1: Run & FWD/REV
B.8 H Parameters: Multi-Function Terminals
Description
Values
Page
Default: 2.0 s
Min.: 0.0
Max.: 10.0
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
B
299