Priority
If multiple sequence timers overlap, the timer with the lowest number has priority.
Sequence Timer 1 = highest priority
Sequence Timer 4 = lowest priority
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4.
If the Stop Time is set to a higher value than the Start Time, the Sequence Timers will be active starting from the set Start
Time, run through midnight, and stop the following day at the set Stop Time.
Note:
Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer in drive software
versions PRG: 8551 and earlier.
No.
S2-01
S2-06
S2-11
S2-16
<1> Default is 00:00 and range is 00:00 to 24:00 when o4-20 is set to 1 (24-hour).
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No.
S2-02
S2-07
S2-12
S2-17
n
S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No.
S2-03
S2-08
S2-13
S2-18
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Name
Sequence Timer 1 Start Time
Sequence Timer 2 Start Time
Sequence Timer 3 Start Time
Sequence Timer 4 Start Time
Name
Sequence Timer 1 Stop Time
Sequence Timer 2 Stop Time
Sequence Timer 3 Stop Time
Sequence Timer 4 Stop Time
Name
Sequence Timer 1 Day Selection
Sequence Timer 2 Day Selection
Sequence Timer 3 Day Selection
Sequence Timer 4 Day Selection
5.11 S: Special Parameters
Setting Range
<1>
12:00AM to 11:59PM
<1>
12:00AM to 11:59PM
<1>
12:00AM to 11:59PM
<1>
12:00AM to 11:59PM
Setting Range
00:00 to 24:00
00:00 to 24:00
00:00 to 24:00
00:00 to 24:00
Setting Range
0 to 10
0 to 10
0 to 10
0 to 10
Default
<1>
12:00AM
<1>
12:00AM
<1>
12:00AM
<1>
12:00AM
Default
00:00
00:00
00:00
00:00
Default
0
0
5
0
0