YASKAWA Z1000U Technical Manual page 208

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

6.4 Fault Detection
HOA Keypad Display
Internal cooling fan has malfunctioned
Fault detected in the internal cooling fan or
magnetic contactor to the power supply
HOA Keypad Display
FB01
Cause
The digital input set to Safety open is open
<1> Parameter Z2-31, Safety Open Message Selection, determines the fault message displayed when FB01 is triggered.
HOA Keypad Display
FB02
Cause
The digital input set to BAS Interlock is open
HOA Keypad Display
FB03
Cause
An external fault (EFB) digital input became
active.
An external fault (EFB) was received from the
serial communications network.
HOA Keypad Display
FB05
Cause
Load is too heavy
Cycle times are too short during acceleration and
deceleration.
A general-purpose motor is driven below the rated
speed with a high load
208
• Cycle power to the drive.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative
operation time of the fan maintenance timer with U4-04.
• Refer to cooling fan replacement instructions in
cooling fan has exceeded its expected performance life or is damaged in any other way.
• Cycle power to the drive.
• If the fault continues to occur, replace the power board/gate drive board or the entire drive.
• Contact Yaskawa or a Yaskawa representative for instructions on replacing the power board/gate
drive board.
<1>
Safety Open
Note:
A fault reset is not required. Bypass contactor K3 is opened.
• Install a NC safety circuit between DI-o and IG-24 on PCB A2
• Install a jumper between DI-2 and IG-24 on PCB A2. Use this method if a safety circuit will be
added in the future or is no safety circuit will be used at all.
BAS Interlock Open Time Out
Note:
A fault reset is required. An EF0 is sent to the drive and bypass contactor K3 is not
affected.
BAS/Damper Interlock Open, Interlock Wait Timer Expired
• Install a NC BAS Interlock Circuit/Damper Interlock between DI-o and IG-24 on PCB A2
• Install a jumper between DI-2 and IG-24 on PCB A2. Use this method if a safety circuit will be
added in the future or is no safety circuit will be used at all.
• Verify that the input assigned for the BAS Interlock is active within the timeout period set in Z1-15.
External Fault Bypass (EFB)
Note:
A fault reset is required. An EF0 is sent to the drive and drive output contactor K2 and
bypass contactor K3 are opened.
External fault to bypass set
Remove the cause of the external fault.
• Remove the cause of the external fault
• Remove the external fault input from the controller.
• Verify that the controller program is correct.
Motor Overload
Note:
A fault reset is required. An EF0 is sent to the drive and bypass contactor K3 is opened.
Motor Overload detected
Reduce the load.
Increase the acceleration and deceleration times (C1-01 and C1-02).
• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Fault Name
Refer to Drive Cooling Fans on page
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
255if the

Advertisement

Table of Contents
loading

Table of Contents