YASKAWA Z1000U Technical Manual page 190

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

5.14 Z: Bypass Parameters
Setting
14
Bypass Mode Selected
15
Drive or Bypass Fault Active
16
Drive Fault Active
17
Bypass Fault Active
18
Auto Transfer Active
19
Serial Run Command Active
20
Damper Actuator Output
21
ON Always
n
Z2-31: Safety Open Message Selection
Sets the fault message displayed when an FB01 fault is triggered. This parameter also determines the text that is displayed on
the top line of the HOA keypad.
No.
Z2-31
Setting 0: Safety Open
Setting 1: Fire Stat
Setting 2: Freeze Stat
Setting 3: Smoke Alarm
Setting 4: Over Pressure
190
Function
Name
Safety Open Message Selection
DIGITAL OPERATOR
ALM
BYP-SAFETY OPEN
UB-01=
0.0A
UB-02=10000101
LSEQ
LREF
UB-03=00001000
RLY
DRV/BYP
LO
ESC
RE
RESET
ENTER
DIGITAL OPERATOR
ALM
RUN
STOP
BYP-FIRE STAT
UB-01=
0.0A
LSEQ
UB-02=10000101
UB-03=00001000
LREF
DRV/BYP
RLY
LO
ESC
RE
RESET
ENTER
DIGITAL OPERATOR
ALM
RUN
STOP
BYP-FREEZE STAT
UB-01=
0.0A
UB-02=10000101
LSEQ
LREF
UB-03=00001000
RLY
DRV/BYP
LO
ESC
RE
RESET
ENTER
DIGITAL OPERATOR
ALM
RUN
STOP
BYP-SMOKE ALARM
UB-01=
0.0A
UB-02=10000101
LSEQ
LREF
UB-03=00001000
RLY
DRV/BYP
LO
ESC
RE
RESET
ENTER
DIGITAL OPERATOR
ALM
RUN
STOP
BYP-OVR PRESSURE
UB-01=
0.0A
LSEQ
UB-02=10000101
UB-03=00001000
LREF
DRV/BYP
RLY
LO
ESC
RE
RESET
ENTER
RUN
STOP
Setting
22
Loss of Load Detected
Run Verify
The digital output closes when the drive or bypass output
23
current exceeds 10% of the value set in E2-01.
The digital output opens when the drive or bypass output
current falls below 5% of the value set in E2-01.
Not Used (Through Mode)
99
This setting allows serial communications to control the
output.
Setting Range
ALM
DIGITAL OPERATOR
BYP-FAULTED
FB01
Safety Open
DRV/BYP
RLY
FWD
LO
ESC
RE
RESET
ENTER
ALM
DIGITAL OPERATOR
RUN
STOP
BYP-FAULTED
FB01
Fire Stat
RLY
FWD
DRV/BYP
LO
ESC
RE
RESET
ENTER
ALM
DIGITAL OPERATOR
RUN
STOP
BYP-FAULTED
FB01
Freeze Stat
RLY
FWD
DRV/BYP
LO
ESC
RE
RESET
ENTER
ALM
DIGITAL OPERATOR
RUN
STOP
BYP-FAULTED
FB01
Smoke Alarm
DRV/BYP
RLY
FWD
LO
ESC
RE
RESET
ENTER
ALM
DIGITAL OPERATOR
RUN
STOP
BYP-FAULTED
FB01
Over Pressure
RLY
FWD
DRV/BYP
LO
ESC
RE
RESET
ENTER
RUN
STOP
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Function
Default
0 to 6
0