C7: Voltage Adjustment
n
C7-60: Output Voltage Limit Mode Selection
Sets the mode to limit the output voltage.
Set this parameter to 0 (Harmonic suppression priority mode) to give priority to harmonic suppression. The maximum output
voltage is automatically limited to suppress harmonics.
Set this parameter to 1 (High output voltage mode) to give priority to the output voltage over harmonic suppression. The
effectiveness of harmonic suppression will be reduced because the maximum output voltage will be used.
No.
C7-60
Setting 0: Harmonic Suppression Priority Mode
Setting 1: High Output Voltage Mode
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Parameter Name
Output Voltage Limit Mode Selection
Setting Range
0, 1
Determined by A1–02
5.3 C: Tuning
Default
5
123