YASKAWA Z1000U Technical Manual page 57

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

n
Enable the Internal EMC Filter
If EMC is a concern and the network is grounded symmetrically, install the SW screw to the ON position. Installing the SW
screw enables the internal EMC filter (Drives are shipped with the SW screw installed at the OFF position).
DANGER! Electrical Shock Hazard. Do not touch SW screw while power is applied to the drive. Failure to comply will result in death or
serious injury.
WARNING! Electrical Shock Hazard. Connect the ground cable correctly. Failure to comply may result in death or serious injury.
NOTICE: When disabling the internal EMC filter, move the screws from ON to OFF and then tighten to the specified torque. Completely
removing the screws or tightening the screws to an incorrect torque may cause drive failure.
Note:
For floating, impedance grounded, or asymmetrically grounded networks, disconnect the internal EMC filter by moving the SW screw to
the OFF position.
Table 3.6
shows asymmetrical grounded networks. Asymmetrical networks require first moving the SW screw to disconnect
the internal ground connection. (Drives are shipped with the SW screw installed at the OFF position.)
Grounded at the corner of the delta
Grounded at the middle of the side
Single-phase, grounded at the end point
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Figure 3.9 Ground Wiring for Multiple Bypass Units
Table 3.6 Asymmetrical Grounded Network
3.4 Input and Output Power Wiring Connections
L3
L3
L1
L2
L1
L2
L1
N
57
3