YASKAWA Z1000U Technical Manual page 135

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

Setting 19: PID Disable
Close a digital input to indefinitely disable the PID function. When the input is released, the drive resumes PID operation.
Refer to PID Block Diagram on page
Setting 24: External Fault
The External fault command stops the drive when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to 24. The HOA keypad will display EFo
where o is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal DI-3, "EF3" will be displayed.
The conditions of setting 24 are:
• Terminal status is normally open
• Detection condition is always detected
• Stopping method is coast to stop.
Setting 60: Motor Pre-Heat 1
A DC current can be circulated through the motor windings to create heat and prevent moisture from condensing on the wire.
Motor Pre-Heating can only be initiated by closing a digital input programmed as a Motor Pre-Heat input (H1-oo = 60). The
level of the DC current used by the Motor Pre-Heat function is determined by b2-09.
A Run input will be given priority over a Motor Pre-Heat input and when the Run command is removed, the motor pre-heating
will resume if the Motor Pre-Heat input is still closed.
u
H2: Multi-Function Digital Outputs
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection
The drive has three multi-function output terminals.
H2-02, and H2-03.
No.
H2-01
H2-02
H2-03
Terminal MD-ME-MF Function Selection (relay)
Setting
0
During Run 1
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock 1 (N.O.)
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
113.
OFF
Motor Pre-Heat 1
command
OFF
FWD Run command
Motor Pre-Heat 1
Output frequency
Figure 5.19 Motor Pre-Heat 1 Input Timing Diagram
Parameter Name
Terminal M1-M2 Function Selection (relay)
Terminal M3-M4 Function Selection (relay)
Table 5.22 Multi-Function Digital Output Terminal Settings
Function
ON
ON
Motor Pre-Heat 1
Start Frequency
(b2-01)
Table 5.22
lists the functions available for theses terminals using H2-01,
Page
Setting
136
B
Torque Detection 1 (N.O.)
136
C
Frequency Reference Loss
136
E
Fault
137
F
Through Mode
137
10
Minor Fault
138
11
Fault Reset Command Active
138
13
Speed Agree 2
138
14
User-Set Speed Agree 2
138
15
Frequency Detection 3
5.7 H: Terminal Functions
OFF
OFF
Motor Pre-Heat 1
braking
Setting Range
0 to 164
0: During Run
0 to 164
1: Zero Speed
0 to 164
2: Speed Agree 1
Function
5
Default
Page
139
139
139
139
139
139
139
139
140
135

Advertisement

Table of Contents
loading

Table of Contents