Connection Diagram; Connection Diagram; Connection Diagram With Drive - YASKAWA CIMR-R5U23P71A Instruction Manual

Power regenerative unit
Table of Contents

Advertisement

3.2

Connection Diagram

Connection Diagram with Drive

Figure 3.1
shows a diagram of a typical connection of the RC5 with the Yaskawa AC Drive.
Note: The RC5 is compatible with other Yaskawa drive (inverter) products. Refer to the application technical manual for the equivalent connection diagram.
Figure 3.1
MCCB
MC
<1> Connect to the terminal (+)1 for 200 V class 0.4 to 22 kW, and 400 V class 0.4 to 45 kW Yaskawa AC drive. Use terminal (+)3 for 200 V class
30 to 37 kW, and 400 V class 55 to 75 kW VS-616G5 drivers or another Yaskawa drive (inverter) product.
<2> Connect the Yaskawa AC Drive power supply terminals R/L1, S/L2, and T/L3 to the secondary side of the power coordinating reactor. Connect
the RC5 AC power supply terminals R/L1, S/L2, and T/L3 to the secondary side of the power suppressing reactor.
<3> Connect terminals r/l 1, s/l 2 of VS-616G5, and terminals r1/l 11, s 1/l 21, and t1/l 31 of the RC5 to the primary side of the power coordinating
reactor.
<4> Make sure to use the specified reactor, fuse and fuse holder.
<5> The sequence input terminal of RC5 is the same as terminal S1.
<6> The wiring distance between the power coordinating reactor, and RC5 and a Yaskawa AC Drive should be 10 m or less.
<7> DC bus wiring [(+) 1 - (+),
<8> Remove the wiring of terminals r/l 1 and s/l 2 since they were connected at the factory.
<9> If installing a circuit breaker or a magnetic contactor on the RC5 output (DC) side to shut down the power supply in an emergency, observe the
following precautions.
• Be sure to confirm that the charge lamps on the RC5 and the Inverter are not lit, and then turn on the circuit breaker or contactor. If the circuit
breaker or contactor is turned on while power is supplied to the RC5 and the Inverter, an overcurrent may occur and damage the circuit breaker or
contactor.
• Be sure to confirm that the circuit breaker or contactor is turned on before the power is turned on for the RC5.
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual
<4>
Power Coordination Reactor
<4>
Current
Suppression
<4>
VS-656RC5
Reactor
FU
R/L1
S/L2
T/L3
r1/
1/
t1/
MOV
CONV
READY
Running
S1
MANUAL RUN
S2
AUTO RUN
S3
EXFLT
S4
RESET
SS
SP
SC
E
Connection Terminal
Figure 3.1 Connection Diagram (When connecting a RC5 and a Yaskawa AC Drive)
] between the Drive and the power regenerative unit should be 5 m or less.
<6>
<8>
<9>
<2>
11
<3>
21
31
M1
M2
M3
M4
<5>
MA
MB
MC
+24V
Sequence
Common
Shield Sheath
AM
Analog Output
-10 to +10V
AC

3.2 Connection Diagram

Yaskawa AC Drive
R/L1
U/T1
<2>
S/L2
V/T2
T/L3
W/T3
r/ 1
<3>
/ 2
<1>
1
IM
25