5.2 b: Application
The PID acceleration/deceleration time can be canceled using a digital input programmed for "PID SFS cancel" (H1-oo =
34).
No.
b5-17
n
b5-18: PID Setpoint Selection
Enables or disables parameter b5-19 for PID setpoint.
No.
b5-18
Setting 0: Disabled
Parameter b5-19 is not used as the PID setpoint.
Setting 1: Enabled
Parameter b5-19 is used as PID setpoint.
n
b5-19: PID Setpoint Value
Used as the PID setpoint if parameter b5-18 = 1.
No.
b5-19
n
b5-20: PID Setpoint Scaling
Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04. The units for setting and display can
be changed with b5-20.
No.
b5-20
Setting 0: 0.01 Hz
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: 0.01% (100.00%: Maximum PID Feedback)
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min (Set the Motor Poles)
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined (Determined by b5-38 and b5-39)
Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID
monitors U1-01 and U1-04.
n
b5-34: PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower limit
is disabled when set to 0.00%
No.
b5-34
n
b5-35: PID Input Limit
Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a
bipolar limit.
No.
b5-35
n
b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID
feedback monitors (U5-01, U5-04).
118
Name
PID Accel/Decel Time
Parameter Name
PID Setpoint Selection
Name
PID Setpoint Value
Parameter Name
PID Setpoint Scaling
Name
PID Output Lower Limit
Name
PID Input Limit
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Setting Range
0.0 to 6000.0 s
Setting Range
0, 1
Setting Range
0.00 to 100.00%
Setting Range
0 to 3
Setting Range
-100.0 to 100.0%
Setting Range
0.0 to 1000.0%
Default
0.0 s
Default
0
Default
0.00%
Default
1
Default
0.00%
Default
1000.0%