Advertisement

5.6 F: Options

5.6
F: Options
u
F6: Drive/Bypass Communications
n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No.
F6-01
Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)
Setting 1: Coast to Stop
Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)
Setting 3: Alarm Only (Continue Operation)
Setting 4: Alarm Only (Continue Operation Using the Frequency Reference Set in d1-04)
Setting 5: Alarm Only (Use the Deceleration Time Set to C1-02)
n
F6-02: External Fault from Bypass Controller Detection Selection
Determines the detection method of an external fault initiated by the bypass controller (EF0).
No.
F6-02
External Fault from Bypass Controller Detection Selection
Setting 0: Always detected
Setting 1: Detection during Run only
n
F6-03: External Fault from Bypass Controller Operation Selection
Determines drive operation when an external fault is initiated by the bypass controller (EF0).
No.
F6-03
External Fault from Bypass Controller Operation Selection
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
132
Parameter Name
Communications Error Operation Selection
Parameter Name
Parameter Name
Setting Range
Setting Range
Setting Range
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Default
0 to 5
Default
0, 1
Default
0 to 3
1
0
1