YASKAWA Z1000U Technical Manual page 313

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
U1-03
Output Current
(0042)
U1-04
Control Method
(0043)
U1-06
Output Voltage
(0045)
Reference
U1-07
DC Bus Voltage
(0046)
U1-08
Output Power
(0047)
U1-10
Input Terminal Status
(0049)
U1-11
Output Terminal Status Output Term Sts
(004A)
U1-12
Drive Status
(004B)
U1-13
Terminal A1 Input Level Term A1 Level
(004E)
U1-14
Terminal A2 Input Level Term A2 Level
(004F)
U1-15
Terminal A3 Input Level Term A3 Level
(0050)
U1-16
Output Frequency after
(0053)
Soft Starter
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Displays the output current.
Output Current
0: V/f Control
Control Method
Displays the output voltage.
Output Voltage
Displays the DC bus voltage.
DC Bus Voltage
Displays the output power (this value is calculated internally).
Output kWatts
Displays the input terminal status.
U1 - 10=
Input Term Sts
Displays the output terminal status.
U1 - 11= 00000000
Verifies the drive operation status.
U1 - 12=
Int Ctl Sts 1
Displays the signal level to analog input terminal A1.
Displays the signal level to analog input terminal A2.
Displays the signal level to analog input terminal A3.
Displays output frequency with ramp time and S-curves. Units
SFS Output
determined by o1-03.
Description
00000000
1
Digital input 1
(terminal S1 enabled)
1
Digital input 2
(terminal S2 enabled)
1
Digital input 3
(terminal S3 enabled)
1
Digital input 4
(terminal S4 enabled)
1
Digital input 5
(terminal S5 enabled)
1
Digital input 6
(terminal S6 enabled)
1
Digital input 7
(terminal S7 enabled)
1
Multi-Function
Digital Output
(terminal MD-ME-MF)
1
Multi-Function
Digital Output
(terminal M1-M2)
1
Multi-Function
Digital Output
(terminal M3-M4)
0
Not Used
1
Fault Relay
(terminal MA-MC closed
MA/MB-MC open)
00000000
1
During run
1
During zero-speed
1
During REV
1
During fault reset
signal input
1
During speed agree
1
Drive ready
1
During alarm
detection
1
During fault detection
B.14 U: Monitors
Analog
Unit
Output Level
10 V: Drive
<1> <2>
rated current
No signal output
available
10 V: 200 Vrms
0.1 Vac
<3>
10 V: 400 V
1 Vdc
<3>
10 V: Drive
rated power
<4>
(kW)
No signal output
available
No signal output
available
No signal output
available
B
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: 100%
0.1%
(-10 to +10 V)
10 V: Max
0.01 Hz
frequency
313